Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log perform monthly fire service test and post log in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers machine room fire extinguisher needs to be recharged, the gauge is on zero it has been discharged, inspection tag is from 2015
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. The one in the machine room is from 2015.
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log A record of findings for firefighters’ service operation required by 8.6.11.1 with identification of the person(s) that performed the operation shall be kept in the machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(b) On-Site Documentation (Procedures for Inspections and Tests) could not get the seismic to trip, provide written instruction in the machine room with the seismic testing procedures
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates fire service phase 1 keyswitch collar markings can no longer be read, replace keyswitch collar (2.27.3.1.1(b)) [non red tag]
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Machine room fire extinguisher inspection tag is from 2013, have the fire extinguisher inspected and tagged annually
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates Fire service phase 1 keyswitch collar markings can no longer be read, replace collar
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 Both front and rear door close force needs to be adjusted so that the pressure is less than 30lbs
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 machine room fire extinguisher inspection tag is expired from 2013, have the fire extinguisher inspected and tagged annually
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Update expired fire extinguisher
conversion conversion n/a repair both the front and rear car door restrictors neither are working 10/25/2019
conversion conversion n/a fire extinguisher is to be inspected and tagged annually, tag is from 2015 10/25/2019
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x fire service phase 2 would not close the door to run the elevator, the door was bouncing on the open limit 6/13/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x the emergency light came on but the alarm bell did not work 6/13/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x both the front and rear door restrictors need to be adjusted so they work 6/13/2023
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x both front and rear door restrictors are not working, adjust and repair door restrictors 6/4/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x Both front and rear door restrictors are not working, repair door restrictors 8/30/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency lights did not come on, repair it so the emergency lights work 8/30/2024