A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
2-WAY COMMUNICATION DEVICE SHALL WORK.Voice works, Camera works, text does not
|
|
|
A17.1-2016 : Elevators
|
5.2 - Bottom clearance, runby, and minimum refuge space
|
2.4.2
|
Yes
|
No
|
Counterweight runby(5") is less than required minimum of 6"
|
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
No
|
No
|
Feeder locations for the main and lighting branch circuits shall be marked on the disconnects.
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
No
|
No
|
A code compliant MCP and related on-site documentation shall be provided in the machine room
|
|
|
A17.1-2016 : Elevators
|
3.2 - Car top light and outlet
|
8.11.2.1.3(b)
|
No
|
No
|
Car top work light does not work.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
No
|
No
|
A data plate, permanently and securely attached, shall be provided in the pit, in the vicinity of the Counterweight buffer indicating Maximum designed counterweight runby
|
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
No
|
No
|
Control Space(6th Floor Lobby) shall have at least one(1) GFCI outlet. Currently no outlet.
|
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
No
|
No
|
An electrical box cover is missing in the overhead and shall be replaced.
|
|
|
A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
8.6.4.13
|
No
|
No
|
Adjust outer upthrust roller bearings for proper clearance to door hanger track.(Floors: 2 & 4)
|
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
No
|
No
|
Pit shall be kept clean. Remove excess debris.
|
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(a)
|
No
|
No
|
A record of firefighters service operation, tested mothly as required by 8.6.11.1, with identification of the person(s) that perfomed the operation and the date shall be avaliable on site.
|
8/14/2026
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
No
|
No
|
Feeder location for the main and lighting branch circuits shall be marked on the disconnects.
|
8/14/2026
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
No
|
No
|
An electrical box cover is missing in the overhead and shall be replaced.
|
8/14/2026
|