MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
x
|
|
Mainline and lighting disconnects need labeling for purpose of each.
|
6/30/2025
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
Machine room door shall be self-closing and self-locking.
|
6/30/2025
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
Machine room door shall have smoke seal around the door.
|
6/30/2025
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
n/a
|
x
|
|
NEC 110.26 - Machine room lighting disconnect does not meet 30" rule/not co-planer.
|
6/30/2025
|
A17.1-2016 : Elevators
|
2.12 - Controller Wiring, Fuses, Grounding, Etc.
|
2.26
|
x
|
|
Machine room lighting disconnect has a fused neutral.
|
6/30/2025
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.1.3
|
x
|
|
Relocate duct smoke detector reset switch to outside machine room.
|
6/30/2025
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
Fill smoke/fire penetrations with approved fire caulk.
|
6/30/2025
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
6/30/2025
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Fire caulk/fill holes and voids in hoistway walls.
|
6/30/2025
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.6.4.13 Door Systems
|
x
|
|
Hoistway sills shall be flush with flooring, currently > 1" gap b/w sill and flooring.
|
6/30/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.4
|
x
|
|
Pit sump pump controller shall be relocated to outside the pit.
|
6/30/2025
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection)
|
x
|
|
Phase 1 fire hat does not work.
|
6/30/2025
|