Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x Machine room door shall be self-closing and self-locking. 6/30/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x Machine room door shall have smoke seal around the door. 6/30/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.1.3 x Relocate duct smoke detector reset switch to outside machine room. 6/30/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Fill smoke/fire penetrations with approved fire caulk. 6/30/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 6/30/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x Mainline and lighting disconnects need labeling for purpose of each. 6/30/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control n/a x NEC 110.26 - Machine room lighting disconnect does not meet 30" rule/not co-planer. 6/30/2025
A17.1-2016 : Elevators 2.12 - Controller Wiring, Fuses, Grounding, Etc. 2.26 x Machine room lighting disconnect has a fused neutral. 6/30/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fire caulk/fill holes and voids in hoistway walls. 6/30/2025
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.6.4.13 Door Systems x Hoistway sills shall be flush with flooring, currently > 1" gap b/w sill and flooring. 6/30/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.4 x Pit sump pump controller shall be relocated to outside the pit. 6/30/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.1.6(h) Audible/Visual Signal (Re-Inspection) x Phase 1 fire hat does not work. 6/30/2025