A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Relocate sump pump controller and related wiring from pit or replace with sump pump without oil sensing capabilities since this is not a hydraulic elevator. 10/9/2025
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 x Exhaust fan at top of hoistway shall not operate when fire service is initiated by a fire alarm initiating device. 10/9/2025
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 x Drop down smoke barriers at hoistway entrances shall be operational. 10/9/2025