| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | x | Drop down smoke barriers at hoistway entrances shall be operational. | 10/9/2025 | |
| A17.1-2016 : Elevators | 3.11 - Hoistway smoke control | 2.1.4 | x | Exhaust fan at top of hoistway shall not operate when fire service is initiated by a fire alarm initiating device. | 10/9/2025 | |
| A17.1-2016 : Elevators | 5.1 - Pit access, lighting, stop switch, and condition | 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) | x | Relocate sump pump controller and related wiring from pit or replace with sump pump without oil sensing capabilities since this is not a hydraulic elevator. | 10/9/2025 |