Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) Yes No Relocate sump pump controller and related wiring from pit, or replace with sump pump without oil sensing capabilities since this is not a hydraulic elevator. 10/9/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test Yes No Grout bottom floor hall sill. 10/9/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No Repair damper on exhaust fan at top of hoistway, top half of damper will not stay closed. 10/9/2025
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 Yes No Exhaust fan at top of hoistway shall not operate when fire service is initiated by a fire alarm initiating device. 10/9/2025
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 Yes No Drop down smoke barriers at hoistway entrances shall be operational. 10/9/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test Yes No Building corridors shall be so lighted that illumination at the landing sills, when an elevator is in service, shall not be less than 10fc. 12/2/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test Yes No Provide lighting at garage level landing same as provided on south car garage landing. 12/2/2025