Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Building corridors shall be so lighted that illumination at the landing sills, when an elevator is in service, shall not be less than 10fc. 12/2/2025
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 x Drop down smoke barriers at hoistway entrances shall be operational. 10/9/2025
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 x Exhaust fan at top of hoistway shall not operate when fire service is initiated by a fire alarm initiating device. 10/9/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Grout bottom floor hall sill. 10/9/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Provide lighting at garage level landing same as provided on south car garage landing. 12/2/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x Relocate sump pump controller and related wiring from pit, or replace with sump pump without oil sensing capabilities since this is not a hydraulic elevator. 10/9/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Repair damper on exhaust fan at top of hoistway, top half of damper will not stay closed. 10/9/2025