MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Building corridors shall be so lighted that illumination at the landing sills, when an elevator is in service, shall not be less than 10fc.
|
12/2/2025
|
|
A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
Drop down smoke barriers at hoistway entrances shall be operational.
|
10/9/2025
|
|
A17.1-2016 : Elevators
|
3.11 - Hoistway smoke control
|
2.1.4
|
x
|
|
Exhaust fan at top of hoistway shall not operate when fire service is initiated by a fire alarm initiating device.
|
10/9/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Grout bottom floor hall sill.
|
10/9/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Provide lighting at garage level landing same as provided on south car garage landing.
|
12/2/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Relocate sump pump controller and related wiring from pit, or replace with sump pump without oil sensing capabilities since this is not a hydraulic elevator.
|
10/9/2025
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Repair damper on exhaust fan at top of hoistway, top half of damper will not stay closed.
|
10/9/2025
|