Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 Yes No Machine room door shall be fire rated. 9/19/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Heat detectors shall be within 24" from sprinkler head. Around sprinkler head shall be fire caulked. 9/19/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No There are two sprinkler heads and only one heat detector. Heat detector which needs to be within 24" from each sprinkler head. 9/19/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 Yes No A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 9/19/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No All smokes and heats need to be tested. 9/19/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 Yes No Machine room door shall be fire rated. 10/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Heat detectors shall be within 24" from sprinkler head. Around sprinkler head shall be fire caulked. One shall be added and one shall be moved. The heat detectors and sprinkler heads shall be fire caulked. 10/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No All smokes and heats need to be tested. 10/14/2025