Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x There are two sprinkler heads and only one heat detector. Heat detector which needs to be within 24" from each sprinkler head. 9/19/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Heat detectors shall be within 24" from sprinkler head. Around sprinkler head shall be fire caulked. One shall be added and one shall be moved. The heat detectors and sprinkler heads shall be fire caulked. 10/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Heat detectors shall be within 24" from sprinkler head. Around sprinkler head shall be fire caulked. 9/19/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x All smokes and heats need to be tested. 10/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x All smokes and heats need to be tested. 9/19/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Machine room door shall be fire rated. 10/14/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Machine room door shall be fire rated. 9/19/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 9/19/2025