| Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
|---|---|---|---|---|---|---|
| A17.1-2016 : Elevators | 5.15 - Overspeed Valve | 8.6.5.16.5 | No | No | OSV valve is not sealed to indicate if its been tested or not, need to test within 30 days | 5/13/2026 |
| A17.1-2016 : Elevators | 1.6 - Car emergency signal | 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) | Yes | No | Emergency bell is inoperable. Re-inspection required | |
| A17.1-2016 : Elevators | 1.5 - Car lighting and receptacles | 2.14.7 | Yes | No | Emergency light is inoperable. Re-inspection required |