Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service (S)1 x repair fire service phase 1 recall, goes to floor opens door and then closes immediatly, could not test fire service phase 2 9/4/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x only one emergency light bulb was working 9/30/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x when the fire service phase 1 keyswitch is turned to the on position, the elevator returns to the recall floor, stops momentarily without opening the doors, then moves away from the recall floor at leveling speed in which ever direction it was traveling when it arrived at the recall floor. when it arrives at the next floor it still does not open the doors. unit was Red Tagged 9/30/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x x We simulated smoke detector activation and the unit responded the same way as when we activated the keyswitch. 9/30/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) Maintenance Control Program documents are missing
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display is from 2019