A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
2.1.1.1 - Fire caulk/fill holes and voids in the hoistway walls, as marked with orange paint.
|
3/13/2026
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Sump pump shall have the capacity to remove a minimum of 11.4 m3/h (3,000 gal/h) per elevator.
|
3/13/2026
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
Sump Pump cover shall have the capacity to flow a minimum of 11.4 m3/h (3,000 gal/h) per elevator to sump pump, be able to support worker weight and be substantially flush to the pit floor as not to create a tripping hazard .
|
3/13/2026
|