Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Door Systems 8.6.4.13 (Re-Inspection) Yes No Bottom landing hoistway door missing a pickup roller. 8/16/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No fire service phase 2 does not override the 3rd floor lockout, make it so fire service overrides the security lockout 6/14/2023
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes fire service phase 2 needs to override the lockout for floor 3, did not red tag the elevator, it will not trap emergency personel, just can't use the elevator to reach top floor on fire service 5/19/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine room fire extinguisher inspection tag expired
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Missing LB cover top of hoistway, hooked to smoke detectors.
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No on fire service phase 2, need to override 3rd floor lockout 6/3/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current copy of the state operating certificate in the machine room
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Post monthly fire service test log in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide access to the complete MCP in the machine room according to 8.6
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display is from 2019