Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.8 x 2.8.3.3.4 - The electrical equipment in the pit located less than 48" above the floor (except earthquake protective devices) shall be weatherproof, and the wiring (except travel cables) shall be identified for use in wet locations. 11/26/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x A separate branch circuit shall supply the car lights, receptacles, auxiliary lighting power source, and ventilation on each elevator car. Note: One of the pit lights are on the same branch circuit as the car lights. Also the pit light switch will only turn off one of the two lights in the pit. These items shall be corrected. 11/26/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 x x Fire service operation and all initiation devices shall be tested. 11/26/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x In electrical equipment rooms, the illumination shall not be controlled by automatic means only. In the elevator machine room, this switch is currently a motion sensor. 11/26/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x The heat detector in the overhead shall be removed. There is a heat and a smoke sensor in the overhead, but no sprinkler in the overhead. 11/26/2024
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x The hole in the hoistway wall for the sump pump discharge pipe must be filled with approved material. 11/26/2024
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27.2 Phase I Emergency Recall Operation Prior to Device Actuation x x The machine room heat detector failed to activate the shunt trip disconnect.
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x The overhead fasteners protruding through the ceiling of the overhead shall be cut off flush to prevent a hazardous situation. 11/26/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x The pit sump pump must be operational. The pump was turning on without the presence of water during the test, and wouldn't turn off. 11/26/2024