Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current copy of the state operating certificate in the machine room
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display is from 2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide access to the complete MCP in the machine room according to 8.6
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods tighten the muffler bolts, the muffler leaks when under relief pressure. The working pressure shall not exceed the component rated pressure of the muffler and fittings used on the pressure side of the hydraulic system. {A17.2-2014 [2.32.1.2(a)]} {A17.1-2016 [3.19.1.2]}
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Post monthly fire service test log in the machine room