A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
8/27/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Smokes and heats need to be re-tested. Note: The outputs from the alarm system to the elevator control will likely need to have the program adjusted because actuation of the smokes doesn't always send the car to the correct floor.
|
10/2/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Smokes and heats need to be tested/inspected, the installation is not complete.
|
8/27/2024
|