Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Operation of the elevator while operating on emergency generator power shall be tested. 2/12/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.3.1.1(q) Yes No Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No 19ft candles required on floor in front of controller. 2/12/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Fire caulk around sheet rock and beams contact point. 2/12/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 Yes No Install all hoistway covers. 2/12/2025
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 Yes No Bevel ledges greater than 4 inches. 2/12/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.3.2 Yes No Counterweight guard does not cover full area of counterweight. 2/12/2025