Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Operation of the elevator while operating on emergency generator power shall be tested. 2/12/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x 19ft candles required on floor in front of controller. 2/12/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fire caulk around sheet rock and beams contact point. 2/12/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Install all hoistway covers. 2/12/2025
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Bevel ledges greater than 4 inches. 2/12/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.3.2 x Counterweight guard does not cover full area of counterweight. 2/12/2025