A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
No active phone line or internet for video.
|
1/16/2025
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
Yes
|
No
|
There is no fire extinguisher at machine space area on 4th floor.
|
1/16/2025
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
Yes
|
No
|
Fourth floor heat detector shall be more than 3' from HVAC venting.
|
1/16/2025
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
Yes
|
No
|
Shunt auxiliary contacts are not functional.
|
1/16/2025
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
Yes
|
No
|
Pit sprinkler piping infringes on car, need to relocate.
|
1/16/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
Yes
|
No
|
Fill hoistway fire penetrations with approved material.
|
1/16/2025
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
Yes
|
No
|
There is no fire extinguisher at machine space area on 4th floor. It shall be provided.
|
4/3/2026
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.11.3.1.1(q)
|
Yes
|
No
|
Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
|
|
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
8.11.2.1.2(p)
|
No
|
No
|
Disconnects are obstructed by building supplies being stored in the Disconnect room. Must maintain at least 36" clearance and keep flammables out of all electrical rooms.
|
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Testing incomplete: Only tested FAID and identified hoistway fire penetrations. Car sill hit pit sprinkler piping, crew attempted repairs. Testing stopped. All acceptance testing shall be completed.
|
1/16/2025
|