Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Testing incomplete: Only tested FAID and identified hoistway fire penetrations. Car sill hit pit sprinkler piping, crew attempted repairs. Testing stopped. All acceptance testing shall be completed. 1/16/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x No active phone line or internet for video. 1/16/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x There is no fire extinguisher at machine space area on 4th floor. 1/16/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x Fourth floor heat detector shall be more than 3' from HVAC venting. 1/16/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Shunt auxiliary contacts are not functional. 1/16/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Pit sprinkler piping infringes on car, need to relocate. 1/16/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fill hoistway fire penetrations with approved material. 1/16/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x There is no fire extinguisher at machine space area on 4th floor. It shall be provided.