Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Operation of the elevator shall be test while on emergency generator power. 2/12/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.11.2.1.1(q) x Elevators that are equipped to operate on Emergency Power shall be tested operating on Em Power, Annually.
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 8.11.2.1.2(p) Disconnects are obstructed by building supplies being stored in the Disconnect room. Must maintain at least 36" clearance and keep flammables out of all electrical rooms.