Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication system shall work. 3/31/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 3.8 x Two 4x4 box covers are missing. 3/31/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Top of hoistway outlet shall be GFCI type. 3/31/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine space lighting shall be at least 19fc and not motion activated. 3/31/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x 1st floor smoke detector shall be located at 1st floor ceiling height. It is currently at 2nd floor ceiling (open air entrance). 3/31/2025
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.1 x Cab lighting disconnect shall be of fused type disconnect. 3/31/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting shall be at least 10fc. 3/31/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Hoistway smoke penetrations shall be fire caulked. 3/31/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Top of hoistway smoke and heat detector shall be relocated at or above sprinkler height and not more than 11" from ceiling, heat not more than 24" from sprinkler. All to be NFPA 72 & 13 compliant. 3/31/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Electrical room smoke and heat detector shall not initiate recall operations of the elevator. 3/31/2025