Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x The overhead fasteners protruding through the ceiling of the overhead shall be cut flush to prevent a hazardous situation. 3/18/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x In electrical equipment rooms, the illumination shall not be controlled by automatic means only. Note: The machine room light shall remain on anytime the switch is in the on position. 3/18/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 x x Spot-type smoke detectors shall be located on the ceiling or, if on a sidewall, between the ceiling and 12 inches down from the ceiling to the top of the detector. Note: The smoke detector in the overhead does not meet these requirements. 3/18/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x All electrical boxes in the machine room shall have covers installed and any knockout holes shall be plugged. 3/18/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Separate branch circuits shall supply the hoistway pit lighting and receptacles. Required lighting shall not be connected to the load side of a ground fault circuit interrupter. 3/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.4 x A clear distance of not less than 4.5 inches from the centerline of the rungs, cleats, or steps to the nearest permanent object in back of the pit ladder shall be provided. 3/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.2 x The pit floor shall be flush. Note: The sump pump grate is protruding from the surface floor creating a potential tripping hazard. This shall be corrected. 3/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x The pit lighting shall provided an illumination of not less than 10 foot-candles at the pit floor. 3/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Mineral wool shall be installed in the overhead where the ceiling meets the wall per Fire Marshall. 3/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x On elevators provided with firefighters' emergency operation, a drain or sump pump shall be provided. the sump pump/drain shall have the capacity to remove a minimum of 3,000 gal/h per elevator. Note: The sump pump provided doesn't appear to meet this requirement after calculating for dynamic head. A higher capacity pump shall be provided. 3/18/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Separate branch circuits shall supply the hoistway pit lighting and receptacles. Required lighting shall not be connected to the load side of a ground fault circuit interrupter. 4/16/2025