Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x The overhead fasteners protruding through the ceiling of the overhead shall be cut flush to prevent a hazardous situation. 3/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x The penetrations in the hoistway wall from the sump pump discharge pipe, oil line, wireway, and sump control shall be filled with approved material. 3/18/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x In electrical equipment rooms, the illumination shall not be controlled by automatic means only. Note: The machine room light shall remain on anytime the switch is in the on position. 3/18/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x All electrical boxes in the machine room shall have covers installed and any knockout holes shall be plugged. 3/18/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Separate branch circuits shall supply the hoistway pit lighting and receptacles. Required lighting shall not be connected to the load side of a ground fault circuit interrupter. 3/18/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x The machine room illumination shall be not less than 19 foot-candles measured at floor level. 3/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.2 x The pit floor shall be flush. Note: The sump pump grate is protruding from the surface floor creating a potential tripping hazard. This shall be corrected. 3/18/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.4 x The machine room shall have a self-closing and self-locking door and shall be operable from the interior space without the use of a key. 3/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x The pit lighting shall provided an illumination of not less than 10 foot-candles at the pit floor. 3/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Mineral wool shall be installed in the overhead where the ceiling meets the wall per Fire Marshall. 3/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x On elevators provided with firefighters' emergency operation, a drain or sump pump shall be provided. the sump pump/drain shall have the capacity to remove a minimum of 3,000 gal/h per elevator. Note: The sump pump provided doesn't appear to meet this requirement after calculating for dynamic head. A higher capacity pump shall be provided. 3/18/2025