Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide access to the complete MCP in the machine room according to 8.6
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13.1(l) Means to restrict hoistway/car door opening (Door Restrictors) (Re-Inspection) x adjust the door restrictor, the hook does not catch 8/16/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements adjust the car door restrictor so that it works
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) repair elevator machine room lighting, only measured 3 foot-candles of illumination at the floor. required to have minimum of 10 foot-candles of illumination at the floor
MO Minimum : Elevators (I) - Pits (I)1 water in the pit, maintain a dry pit
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Post monthly fire service test log in the machine room
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log the monthly fire service test log has not been filled out since January 2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display is from 2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current copy of the state operating certificate in the machine room