A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
x
|
|
Machine room lighting shall not be less than 19fc at floor.
|
8/24/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Machine room floor drain not allowed in the machine room. It is creating a trip hazard.
|
8/24/2024
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
x
|
|
Machine room ventilation required, either natural or mechanical.
|
8/24/2024
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Pit sump pump shall not drain into machine room.
|
8/24/2024
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Hoistway fire penetrations, gaps, cracks shall be sealed (also around door frames).
|
8/24/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Pit sprinkler supply line infringes on car door opening fully.
|
8/24/2024
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
3.8
|
x
|
|
Pit electrical boxes shall be weatherproof due to pit sprinkler.
|
8/24/2024
|