Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Hoistway fire penetrations, gaps, cracks shall be sealed (also around door frames). 8/24/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Machine room floor drain not allowed in the machine room. It is creating a trip hazard. 8/24/2024
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 x Machine room lighting shall not be less than 19fc at floor. 8/24/2024
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Machine room ventilation required, either natural or mechanical. 8/24/2024
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 3.8 x Pit electrical boxes shall be weatherproof due to pit sprinkler. 8/24/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard x Pit sprinkler supply line infringes on car door opening fully. 8/24/2024
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Pit sump pump shall not drain into machine room. 8/24/2024