A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
x
|
|
Top of common wall between hoistways shall be beveled no less than 75 degrees.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
3.3 - Top-of-car operating device
|
2.14.1.7
|
x
|
|
Install railing on cartop.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
Patch holes and voids in machine room especially at top of walls and where piping passes through to hoistway.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Remove old unused sprinkler piping from top of hoistway.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Replace flexible metal conduit with EMT from fire alarm system relays to elevator controllers in machine room. Cannot be longer than 6" in length.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Replace flexible metal conduit with EMT from disconnect to climate control unit in machine room. Cannot be longer than 6" in length.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Cover hole where hydraulic supply line and sump pump discharge line pass through hoistway wall between pits at pit floor level.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Patch holes on hoistway side of wall where hydraulic supply line passes into machine room.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Fire caulk and fill voids around hoistway side of entrance frames.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Fire caulk and seal around room side of hoistway entrance frames.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Install emergency two-way communications device in car.
|
6/18/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Box on 1st floor that hall station is mounted to needs to be replaced with a deeper box so hall station plate will fit flush with no gap.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
x
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
6/18/2025
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
6/18/2025
|