Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Install emergency two-way communications device in car. 6/18/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x Heat detector in machine room is more than 24" from sprinkler head and needs to be moved. 6/18/2025
A17.1-2016 : Elevators 2.4 - Machine space 2.7.1 x Patch holes in machine room. 6/18/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2 On-Site Documentation x A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. 6/18/2025
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 x A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room. 6/18/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8 x Conduit carrying incoming power to pump unit must be raised to allow for future pump/motor replacement. Components cannot be replaced where the pipe is currently located. 6/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Fire caulk and fill voids on hoistway side of entrance frames. 6/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Fire caulk and seal around room side of entrance frames. 6/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Fire caulk around sprinkler pipe where it passes into front of hoistway above first floor entrance. 6/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Seal around ductwork where it passes between hoistway wall above first floor entrance. 6/18/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 3.1 x Patch holes around hydraulic supply line and sump pump discharge line at pit floor level. 6/18/2025
A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 2.8 x Remove old unused sprinkler piping from overhead. 6/18/2025
A17.1-2016 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.1.6 x Top of common wall between hoistways shall be beveled no less than 75 degrees. 6/18/2025
A17.1-2016 : Elevators 3.3 - Top-of-car operating device 2.14.1.7 x Install railing on cartop. 6/18/2025