A17.1-2016 : Elevators
|
3.13 - Windows, projections, recesses, and setbacks
|
2.1.6
|
x
|
|
Top of common wall between hoistways shall be beveled no less than 75 degrees.
|
6/18/2025
|
A17.1-2016 : Elevators
|
3.3 - Top-of-car operating device
|
2.14.1.7
|
x
|
|
Install railing on cartop.
|
6/18/2025
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
Patch holes in machine room.
|
6/18/2025
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Conduit carrying incoming power to pump unit must be raised to allow for future pump/motor replacement. Components cannot be replaced where the pipe is currently located.
|
6/18/2025
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
2.8
|
x
|
|
Remove old unused sprinkler piping from overhead.
|
6/18/2025
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Fire caulk and fill voids on hoistway side of entrance frames.
|
6/18/2025
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Fire caulk and seal around room side of entrance frames.
|
6/18/2025
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Fire caulk around sprinkler pipe where it passes into front of hoistway above first floor entrance.
|
6/18/2025
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Seal around ductwork where it passes between hoistway wall above first floor entrance.
|
6/18/2025
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
3.1
|
x
|
|
Patch holes around hydraulic supply line and sump pump discharge line at pit floor level.
|
6/18/2025
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Install emergency two-way communications device in car.
|
6/18/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.10 Acceptance Inspection and Test
|
x
|
|
Heat detector in machine room is more than 24" from sprinkler head and needs to be moved.
|
6/18/2025
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.2 On-Site Documentation
|
x
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room.
|
6/18/2025
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
A current tested & tagged ABC type fire extinguisher shall be provided in the elevator machine room.
|
6/18/2025
|