MO Minimum : Elevators
|
(A) - Hoistways
|
(A)10
|
x
|
|
The top pull chain used to open the hall door is not working.
|
|
MO Minimum : Elevators
|
(F) - Electrical Switches
|
(F)1
|
x
|
|
The emergency stop switch is not working.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.8 Switch Keys
|
|
|
fire service key is not the same as the other elevators in the building, change the fire service phase 1 and 2 keys to FEOK1
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
machine room state operating certificate is from 2017, update with new copy when received from the state annually
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the copy of the state operating certificate in the machine room is to be updated annually
|
1/20/2021
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
the state operating certificate in the machine room expired in 2017, update with a current copy when received from the state
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
machine room fire extinguisher does not have a current inspection tag, it is to be inspected and tagged annually
|
1/20/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Perform monthly fire service test and post test log in the machine room
|
1/20/2021
|