Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Elevator needs tested under emergency power 4/14/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability Yes No System testing remains 4/14/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 Yes No Increase the machine room illumination to 19fc minimum 4/14/2025
A17.1-2016 : Elevators 2.1 - Access to machine space 2.7.3.1 Yes No space - 2.7.3.3 - Access ladders shall conform to ANSI A17.1 2.7.3.3.1. Offset steps are not aliowed 4/14/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 No No The elevator pit light switch fails to turn off the pit lighting. The electrical wiring deficiency shall be corrected to operate as required.