A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
Elevator needs tested under emergency power
|
4/14/2025
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
Yes
|
No
|
System testing remains
|
4/14/2025
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.9.1
|
Yes
|
No
|
Increase the machine room illumination to 19fc minimum
|
4/14/2025
|
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.1
|
Yes
|
No
|
space - 2.7.3.3 - Access ladders shall conform to ANSI A17.1 2.7.3.3.1. Offset steps are not aliowed
|
4/14/2025
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
No
|
No
|
The elevator pit light switch fails to turn off the pit lighting. The electrical wiring deficiency shall be corrected to operate as required.
|
|