Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 No No The elevator pit light switch fails to turn off the pit lighting. The electrical wiring deficiency shall be corrected to operate as required.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No Increase Machine illumination to 19ft candles throughout, measured at the floor 4/14/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Test emergency standby power 4/14/2025
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 2.27.3 Yes Yes Test phase 1 and 2 fire recall 4/14/2025