A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2.3 (Elevator Emergency Power Illuminated Signal)
|
No
|
No
|
The “Emergency Power” jewel failed to illuminate during emergency power testing, repair jewel to operate as required.
|
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Car Emergency System (Re-Inspection)
|
Yes
|
No
|
The emergency car lighting is not operational. The fixture shall be repaired to operate. Reinspection required.
|
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
Yes
|
No
|
The standby selection switch is inoperative and shall be made to work as designed.
|
|