A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Pit sump controls need to be relocated outside of pit.
|
3/6/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.5 Sump Pump Required/Capacity (Re-Inspect)
|
x
|
|
Pit sump shall be plugged in and tested.
|
3/6/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.6 Sump Pump Covers
|
x
|
|
Pit sump needs proper cover.
|
3/6/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit lighting shall not be controlled by motion.
|
3/6/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit lighting shall be at least 10fc at pit floor.
|
3/6/2025
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.1
|
x
|
|
Disconnects shall have feeder location labels.
|
3/6/2025
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
All FAID shall be tested. No one present to test at this time.
|
3/6/2025
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
Fire alarm initiating devices are not interfacing with elevator controls properly. This shall be corrected and re-tested.
|
3/19/2025
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
2.7.1
|
x
|
|
Seal fire/smoke penetrations in machine room.
|
3/6/2025
|
A17.1-2016 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
|
3/6/2025
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
x
|
|
Machine room lighting shall not be controlled by motion sensor.
|
3/6/2025
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
x
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
3/6/2025
|