Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x 2.8.2.1 Installation of electrical equipment and wiring shall conform to NFPA 70 or CSA C22.1, whichever is applicable (see Part 9). 3 PHASE WIRING SHALL BE PIPED INTO CONTROLLER. NO GREENFILED FLEX OVER 6FT IN LENGHTH. (BATTERY BACKUP WIRING AT TOP OF HOISTWAY, CONTROLLER 3 PHASE POWER WIRING, MISC FLEX IN TOP OF HOISTWAY.) 10/16/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers x 2.2.2.6 Sumps and sump pumps in pits, where provided, shall be covered. The cover shall be secured and level with the pit floor. 10/16/2025
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 2.1.4 x 2.1.4 Control of Smoke and Hot Gases When required by the building code, hoistways shall be provided with means to prevent the accumulation of smoke and hot gases. FIRE CAULKING & COVERING OF WOOD IN HOISTWAY, SEALING PENETRATIONS. 10/16/2025