Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates x The governor and safeties must be tagged after performing the test and identify the name of the person or firm performing the test, the applicable code requirement(s) and date(s) performed. The person performing the test was not supplied with test tags. 4/10/2025
A17.1-2016 : Elevators 1.8 - Door closing force 8.6.4.19.8 x The door torque shall be tested. 4/10/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x The governor shall be tested to determine setting speed, sealed, and tagged. 4/10/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.10 Acceptance Inspection and Test x The governor pull thru and pull out shall be tested. 4/10/2025
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 2.17.9.2 x x 2.17.9.4 - The safeties shall operate as required, providing a compressive stopping action on each guide rail and on each side of the guide rail section. After the test was complete, it was apparent that the jaw on the right hand side of the car did not operate. 4/10/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.5 Sump Pump Required/Capacity (Re-Inspect) x In elevators provided with Firefighters' emergency operation, a drain or sump pump shall be provided. The sump pump/drain shall have the capacity to remove a minimum of 3,000 gal/hour per elevator. The sump pump does not appear to meet this requirement after calculating for dynamic head. 4/10/2025