Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 2.27.1 x not able to test fire int . devices
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.6 Verification of Telephone Operability no telephone line verification switch or light
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x phone works but ansering serv couldnt tell me wher call was coming from
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 need receptical in control space NEC 620.23(C)
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag) x x Bldg phone line needed 7/14/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Pebo not working. Need larger supply wires. 7/14/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x x Heat sensors needed for shunt trip by sprinkler heads. 7/14/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.4 x Sump pump can't be on gfci plug 7/14/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.4.19.6 x x Ffs needs to be tested after heat sensors are installed for shunt trip. 7/14/2025
A17.1-2016 : Elevators 3.8 - Top emergency exit 2.26.2.18 x x Cartop emergency exit switch broken. 7/14/2025
A17.1-2016 : Elevators 2.13 - Governor, Overspeed Switch, and Seal 8.10.2.2.2(hh) x x Governor pullout/thru must be tested 7/14/2025