A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.1 Emergency communications and alarm not functioning (Red Tag)
|
x
|
x
|
Bldg phone line needed
|
7/14/2025
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Pebo not working. Need larger supply wires.
|
7/14/2025
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
x
|
Heat sensors needed for shunt trip by sprinkler heads.
|
7/14/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.4
|
x
|
|
Sump pump can't be on gfci plug
|
7/14/2025
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.4.19.6
|
x
|
x
|
Ffs needs to be tested after heat sensors are installed for shunt trip.
|
7/14/2025
|
A17.1-2016 : Elevators
|
3.8 - Top emergency exit
|
2.26.2.18
|
x
|
x
|
Cartop emergency exit switch broken.
|
7/14/2025
|
A17.1-2016 : Elevators
|
2.13 - Governor, Overspeed Switch, and Seal
|
8.10.2.2.2(hh)
|
x
|
x
|
Governor pullout/thru must be tested
|
7/14/2025
|
A17.1-2016 : Elevators
|
6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators
|
2.27.1
|
x
|
|
not able to test fire int . devices
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1.1.6 Verification of Telephone Operability
|
|
|
no telephone line verification switch or light
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
phone works but ansering serv couldnt tell me wher call was coming from
|
|
A17.1-2016 : Elevators
|
2.3 - Lighting and receptacles
|
2.8.2
|
|
|
need receptical in control space NEC 620.23(C)
|
|