A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
x
|
|
Fire caulk/fill holes and voids in hoistway walls.
|
1/24/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.4
|
x
|
|
Sump pump discharge piping infringes on pit refuge space and car clearance.
|
1/24/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.5
|
x
|
|
Pit lighting shall be at least 10fc at ladder base.
|
1/24/2025
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The in car emergency telephone is not working. Take corrective action and re-test. Note: A variance must be applied for to allow video/text communication.
|
1/27/2025
|
A17.1-2016 : Elevators
|
2.8 - Pipes, wiring, and ducts
|
2.8.2
|
x
|
|
Disconnects shall be labeled with location of feeder breakers.
|
1/24/2025
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
3.26.1
|
x
|
|
Disconnects do not meet 30" rule/not co-planer.
|
1/24/2025
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work.
|
1/24/2025
|