Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 3.26.1 x Disconnects do not meet 30" rule/not co-planer. 1/24/2025
A17.1-2016 : Elevators 2.8 - Pipes, wiring, and ducts 2.8.2 x Disconnects shall be labeled with location of feeder breakers. 1/24/2025
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 x Fire caulk/fill holes and voids in hoistway walls. 1/24/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.5 x Pit lighting shall be at least 10fc at ladder base. 1/24/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.4 x Sump pump discharge piping infringes on pit refuge space and car clearance. 1/24/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The in car emergency telephone is not working. Take corrective action and re-test. Note: A variance must be applied for to allow video/text communication. 1/27/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Two-way communication device shall work. 1/24/2025