Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 3.10 - Hoistway construction 8.7.2.1.1 Hoistway Enclosure Walls x Break off drywall screws projecting thorugh front wall of hoistway. 1/19/2026
A17.1-2016 : Elevators 3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.6.4.19.17 Earthquake Operation x Seismic operation not functioning. 1/19/2026
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.3.7 Phase 2 Operation Panel x Security keypad installed but not operational. Re-inspection is required once the system is operational to ensure fire service activates properly. 1/19/2026
A17.1-2016 : Elevators 5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions 2.26.2.9 Car Safety Mechanism Switch x Safety operated swtich under car shall operate. 1/19/2026