A17.1-2016 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
2.26.2.9 Car Safety Mechanism Switch
|
x
|
|
Safety operated swtich under car shall operate.
|
1/19/2026
|
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.3.7 Phase 2 Operation Panel
|
x
|
|
Security keypad installed but not operational. Re-inspection is required once the system is operational to ensure fire service activates properly.
|
1/19/2026
|
|
A17.1-2016 : Elevators
|
3.34 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater)
|
8.6.4.19.17 Earthquake Operation
|
x
|
|
Seismic operation not functioning.
|
1/19/2026
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
8.7.2.1.1 Hoistway Enclosure Walls
|
x
|
|
Break off drywall screws projecting thorugh front wall of hoistway.
|
1/19/2026
|