MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current copy of the state operating certificate in the machine room
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Post monthly fire service test log in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide access to the complete MCP in the machine room according to 8.6
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Machine room fire extinguisher inspection tag expired
|
|
A17.1-2016 : Elevators
|
2.7 - Fire Extinguisher
|
8.11.3.1.2(j)
|
|
|
the machine room fire extinguisher was last tagged in 2015, have the fire extinguisher inspected and tagged annually
|
|
A17.1-2016 : Elevators
|
2.40 - Maintenance Records
|
8.6.1.2.1(c)
|
|
|
Maintenance Control Program on site documents are missing
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display is from 2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
machine room fire extinguisher inspection tag is expired, have extinguisher inspected and tagged annually
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Machine room fire extinguisher inspection tag is expired, have the fire extinguisher inspected and tagged
|
|
A17.1-2016 : Elevators
|
1.5 - Car lighting and receptacles
|
8.11.3.1.1(e)
|
|
|
replace the emergency light battery, it is dead.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.7 - Fire Extinguisher
|
8.6.1.6.5
|
|
|
Update expired fire extinguisher
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Repair the emergency phone, it automatically hangs up before able to talk to campus police
|
6/3/2020
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
The emergency phone hangs up as soon as the campus police answer the phone, neither side has a chance to talk before it disconnects
|
7/28/2021
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
3.27
|
x
|
x
|
The fire service phase 1 keyswitch would not reset the elevator and put is back into normal operation, had to reset the elevator from the controller. All other features of fire service worked.
|
7/28/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
Emergency lights did not come on, the alarm bell did work. repair emergency lights so they work
|
8/30/2024
|