Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.7 - Fire Extinguisher 8.11.3.1.2(j) No No the machine room fire extinguisher was last tagged in 2015, have the fire extinguisher inspected and tagged annually
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.1(c) No No Maintenance Control Program on site documents are missing
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display is from 2019
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.11.3.1.1(e) No No replace the emergency light battery, it is dead.
A17.1-2016 : Elevators 1.6 - Car emergency signal 2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The emergency phone hangs up as soon as the campus police answer the phone, neither side has a chance to talk before it disconnects 7/28/2021
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 3.27 Yes Yes The fire service phase 1 keyswitch would not reset the elevator and put is back into normal operation, had to reset the elevator from the controller. All other features of fire service worked. 7/28/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Update expired fire extinguisher
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No machine room fire extinguisher inspection tag is expired, have extinguisher inspected and tagged annually
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.7 - Fire Extinguisher 8.6.1.6.5 No No Machine room fire extinguisher inspection tag is expired, have the fire extinguisher inspected and tagged
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting Yes No Emergency lights did not come on, the alarm bell did work. repair emergency lights so they work 8/30/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Repair the emergency phone, it automatically hangs up before able to talk to campus police 6/3/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current copy of the state operating certificate in the machine room
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log No No Post monthly fire service test log in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Provide access to the complete MCP in the machine room according to 8.6
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Machine room fire extinguisher inspection tag expired