MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
This is a winding drum traction residential elevator in a commercial setting. A variance will need to be applied for with the state of Missouri for this unit to remain in a commercial setting.
|
12/4/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency communication shall be installed in the car.
|
12/4/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
x
|
x
|
Need door guards installed on all 3 hall/hoistway doors. Elevator Red Tagged.
|
12/4/2025
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The machine room door shall be self-closing, self-locking and shall be operable from the interior space without the use of a key.
|
11/21/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
This is a winding drum traction residential elevator in a commercial setting. A variance will need to be applied for with the state of Missouri for this unit to remain in a commercial setting.
|
|