MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(2)(C) Re-Inspection Required to Enforce.
|
x
|
|
8.6.5.8 - Possible single bottom jack. Installation year says 2002, but it appears this unit was an older unit that was modernized around 2002. Provide documentation to prove unit does not have a single bottom jack.
|
1/31/2025
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
There is no phone line.
|
1/31/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Door Systems 8.6.4.13 (Re-Inspection)
|
x
|
|
Check the hoistway door closers for proper closing.
|
1/31/2025
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Machine room door shall be fire rated and shall be self-closing and self-locking.
|
1/31/2025
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
x
|
|
Guard or gutter pipes conveying water over the pump unit.
|
1/31/2025
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)5 (Machine Room Lighting)
|
x
|
|
Permanent code compliant lighting shall be provided in the machine room.
|
1/31/2025
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)8
|
x
|
|
Main line disconnect to be moved. Currently over the pump unit flush to the wall next to the controller. There is no working clearance.
|
1/31/2025
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)6 (Pit Lighting)
|
x
|
|
The pit light shall be operational and shall be guarded.
|
1/31/2025
|
MO Minimum : Elevators
|
(K) - Car Platforms and Car Slings
|
(K)4
|
x
|
|
There is no data tag on the controller or crosshead.
|
1/31/2025
|
A17.1-1996 : Elevators
|
2.10 - Numbering of elevators, machines, and disconnect switches
|
211.9
|
x
|
|
Hoistway doors shall be numbered.
|
1/31/2025
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Machine room smoke detector needs to be relocated to a code compliant location.
|
1/31/2025
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
All smoke and heat detectors shall be landed into the controller and checked from proper operation and function.
|
1/31/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
x
|
|
An MCP is required on-site.
|
1/31/2025
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
x
|
|
There are leaky joints on hydraulic line. Take corrective action as needed.
|
1/31/2025
|