Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (C) - Car Enclosure: Freight (C)5 need to have two working ligh fixtures in the car
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair pit light, it did not work. possible burnt out bulb
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x Replace the emergency light battery, it is dead 6/4/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current copy of the state operating certificate in the machine room
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records Provide access to the complete MCP in the machine room according to 8.6
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements bottom landing freight door hoistway access pull chain cover lock is broken and needs to be repaired
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x replace the emergency light battery, it is almost dead 8/16/2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. the one in the room is from 2016
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.7 Record of Oil Usage could not find the any of the oil record logs, logs are to be kept in the machine room for 5 years.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy annually. the certificate on display in the machine room is from 2017
MO Minimum : Elevators (A) - Hoistways (A)5 Replace missing pull strap on level B hoistway door
MO Minimum : Elevators (I) - Pits (I)1 Water in the pit, unclogged floor drain in the pit
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light does not work no lightbulb in fixture, replace lightbulb
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Recovery pump in the pit needs to be replaced with a 5 gallon bucket per state memo 6 (8.6.5.5.2)