Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 2.4 - Machine space 8.6.1.6.5 Fire Extinguishers Yes No ABC Fire Extinguisher is missing. Shall be mounted directly adjacent to door. 5/12/2026
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.11.1 Yes No Car sills to be substantially flush with the floor surface. 5/12/2026
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No Electrical box covers shall be installed. 5/12/2026
A17.1-2016 : Elevators 3.10 - Hoistway construction 2.1 Yes No Fire caulk/fill holes and voids in Hoistway walls, as marked with Orange Paint. 5/12/2026
A17.1-2016 : Elevators 3.11 - Hoistway smoke control 8.10.2.2.3(q) Yes No Guarding of Counterweights in a Multiple-Elevator Hoistway - Counterweight shall be guarded then length of the hoistway. 5/12/2026
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No HVAC/Ventilation system shall work. 5/12/2026
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Inspection incomplete. FAID, door pressure, communication loss, and rescue phone remain to be tesed. 5/12/2026
A17.1-2016 : Elevators 4.2 - Hoistway doors 2.11 Yes No Landing sills to be substantially flush with the floor surface of the elevator landings. 5/12/2026
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No Outlets and Switches shall have covers installed. 5/12/2026
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No Smoke detector shall not be less than 36” from HVAC Vents. 5/12/2026
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No Smoke/fire penetrations to be filled with proper fire caulking. 5/12/2026
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No Sprinkler piping that enters room to feed MR sprinklers cannot exit room and feed other sprinklers. Sprinkler risers and return piping have to be located outside the machine room. 5/12/2026