|
A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
Yes
|
No
|
Car sills to be substantially flush with the floor surface.
|
5/12/2026
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
Yes
|
No
|
Inspection incomplete. FAID, door pressure, communication loss, and rescue phone remain to be tesed.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
Sprinkler piping that enters room to feed MR sprinklers cannot exit room and feed other sprinklers. Sprinkler risers and return piping have to be located outside the machine room.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
Electrical box covers shall be installed.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
Smoke detector shall not be less than 36” from HVAC Vents.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
Smoke/fire penetrations to be filled with proper fire caulking.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
HVAC/Ventilation system shall work.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.4.8 Machine Room and Machinery Space
|
Yes
|
No
|
Outlets and Switches shall have covers installed.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
2.4 - Machine space
|
8.6.1.6.5 Fire Extinguishers
|
Yes
|
No
|
ABC Fire Extinguisher is missing. Shall be mounted directly adjacent to door.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
3.10 - Hoistway construction
|
2.1
|
Yes
|
No
|
Fire caulk/fill holes and voids in Hoistway walls, as marked with Orange Paint.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
2.11
|
Yes
|
No
|
Landing sills to be substantially flush with the floor surface of the elevator landings.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
Yes
|
No
|
Fire caulk/fill holes and voids in Pit wall - sump discharge pipe.
|
5/12/2026
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.2.4
|
Yes
|
No
|
Sump pump discharges onto a floor drain in room adjacent to hoistway, shall discharge so that water does not floor room.
|
5/12/2026
|